General recommendations

Distribution-Grip dead-ends are recommended for termination of bare or jacketed conductors used in distribution constructions. The high mechanical strength, short length, and interchangeability among different conductor sixe meet the requirement of all categories of distribution lines.

 

Jacketed Conductors

Distribution-Grip dead-ends, manufactured from galvanized steel are recommended for direct application on the jacketed conductors

 

Rated holding strength

For bare homogenous conductors, the holding strengths shown on the data sheets approximate the rated breaking strength of the conductor. If used with ACSR the rated holding strength approximates the full strength of aluminum strand plus a percentage of the steel core. Holding strength for jacketed conductor is dependent upon construction.

 

Vibration Dampers

The use of Spiral Vibration Damper should be considered for areas experiencing a history of vibration.

 

Material used

Destruction-Grip dead-ends are made of material compatible with the conductor to which they are applied

 

Application and inspection

Ensure the correct size fitting is used. For detailed method of installation refer to application instructions.

 

Recommended fittings

(Important dimensions to be taken into account when selecting suitable types of thimble)

 

Distribution-Grip dead-end loops are designed for use with a variety of thimbles, clevis thimble and insulators, all of which should have smoothly contoured surfaces and adequate groove widths and loop diameters.

 

Production Characteristics

  • Crossover Marks: Indicate starting point for application
  • Color code: assists in identification of strands size.
  • Identification label: Shows catalogue number and strand diameter range.
  • Lay direction: Must be same as that of the outer layer of the strand to which it is applied

 

Distribution-Grip Dead-end for Bare Conductors (Galvanized steel wire)

Catalog
Number
Cable Range
(inches)
ACSR AAC (All-Al.) AAAC
(All-Al.
Alloy)
Comp.
ACSR
AWAC
1/6
Wt.
Per
100
(lbs.)
Unit
Per
carton
Length
(in.)
Color
Code
Min Max
KDG-2754 .182 .203 #6,6/1 #6,7W #6,7W #6,6/1 - 14 100 16 Blue
KDG-2741 .229 .257 #4,6/1
#4,7/1
#4,7W #4,7W #4,6/1 #4 20 100 17 Orange
KDG-2742 .290 .325 #2,6/1
#2,7/1
#2,7W #2,7W #2,6/1 #2 33 100 24 Red
KDG-2743 .326 .364 #1,6/1 #1,7W #1,7W #1,6/1 #1 44 100 26 Green
KDG-2744 .365 .409 1/0,6/1 1/0,7W 1/0,7W 1/0,6/1 1/0 61 50 26 Yellow
KDG-2745 .410 .460 2/0,6/1 2/0,7W 2/0,7W 2/0,6/1 2/0 61 50 28 Blue
KDG-2746 .461 .516 3/0,6/1 3/0,7W 3/0,7W 3/0,6/1 3/0 88 25 32 Orange
KDG-2747 .517 .577 4/0,6/1 4/0,7W 4/0,7W 4/0,6/1 4/0 125 25 34 Red
KDG-2748 .578 .653 266.8,18/1 266.8,19W 266.8,19W 336.4,18/1 - 168 25 35 Black
KDG-2749 .654 .739 336.4,18/1 336.4,19W 336.4,19W 397.5,18/1 - 220 25 39 Green
KDG-2750 .740 .837 397.5,18/1
477,36/1
477,18/1
450,19W
477,19W
500,37W
397.5,19W 477,18/1
556,19W
- 383 20 45 Orange
KDG-2751 .838 .947 556.5,36/1
605,36/1
636,18/1
556.5,37W
636,37W
650,61W
477,19W
556.5,19W
636,18/1
795,19W
- 506 10 49 Blue
KDG-2752 .948 1.07
1
666.6,36/1
715.5,36/1
795,36/1
715.5,37W
750,61W
795,61W
636,37W 874.5,37W
954,37W
- 667 10 55 Brown
KDG-2753 1.07
2
1.21
2
874.5,36/1
954,36/1
1033.5,36/1
874.5,61W
964,61W
1033.5,61W
795,37W   - 1,087 5 65 Orange

Right-hand lay direction
Raw material: Galvanized steel wire

 

Distribution-Grip Dead end for Bare Conductors (Aluminum clad steel wire)

Catalog
Number
Cable Range
(inches)
ACSR AAC (All-Al.) AAAC
(All-Al.
Alloy)
Comp.
ACSR
AWAC
1/6
Wt.
Per
100
(lbs.)
Unit
Per
carton
Length
(inches)
Color
Code
Min Max
KDG-1554 .182 .203 #6,6/1 #6,7W #6,7W #6,6/1 - 13 100 16 Blue
KDG-1541 .229 .257 #4,6/1
#4,7/1
#4,7W #4,7W #4,6/1 #4 18 100 17 Orange
KDG-1542 .290 .325 #2,6/1
#2,7/1
#2,7W #2,7W #2,6/1 #2 31 100 24 Red
KDG-1543 .326 .364 #1,6/1 #1,7W #1,7W #1,6/1 #1 42 100 26 Green
KDG-1544 .365 .409 1/0,6/1 1/0,7W 1/0,7W 1/0,6/1 1/0 53 50 26 Yellow
KDG-1545 .410 .460 2/0,6/1 2/0,7W 2/0,7W 2/0,6/1 2/0 57 50 28 Blue
KDG-1546 .461 .516 3/0,6/1 3/0,7W 3/0,7W 3/0,6/1 3/0 81 25 32 Orange
KDG-1547 .517 .577 4/0,6/1 4/0,7W 4/0,7W 4/0,6/1 4/0 116 25 34 Red
KDG-1548 .578 .653 266.8,18/1 266.8,19W 266.8,19W 336.4,18/1 - 146 25 35 Black
KDG-1549 .654 .739 336.4,18/1 336.4,19W 336.4,19W 397.5,18/1 - 200 25 39 Green
KDG-1550 .740 .837 397.5,18/1
477,36/1
477,18/1
450,19W
477,19W
500,37W
397.5,19W 477,18/1
556,19W
- 333 20 50 Orange
KDG-1551 .838 .947 556.5,36/1
605,36/1
636,18/1
556.5,37W
636,37W
650,61W
477,19W
556.5,19W
636,18/1
795,19W
- 440 10 55 Blue
KDG-1552 .948 1.071 666.6,36/1
715.5,36/1
795,36/1
715.5,37W
750,61W
795,61W
636,37W 874.5,37W
954,37W
- 628 10 62 Brown
KDG-1553 1.072 1.212 874.5,36/1
954,36/1
1033.5,36/1
874.5,61W
964,61W
1033.5,61W
795,37W - - 890 5 70 Orange

Right-hand lay direction
Raw material: Aluminum clad steel wire

 

Distribution-Grip Dead-end for Jacketed Conductor (Galvanized steel wire)

Catalog
Number
Cable Range
(inches)
Wt.
/Lbs.
Per100
Units
per
carton
Length
(inches)
Color
Code
Min Max
KDG-J2710 .229 .257 20 100 18 Orange
KDG-J2711 .258 .289 35 100 21 Yellow
KDG-J2712 .290 .325 40 100 26 Red
KDG-J2713 .326 .364 60 100 27 Green
KDG-J2714 .365 .409 60 100 27 Yellow
KDG-J2715 .410 .460 90 50 29 Blue
KDG-J2716 .461 .516 90 50 31 Orange
KDG-J2717 .517 .577 130 50 34 Purple
KDG-j2100 .578 .653 180 25 35 Blue
KDG-J2101 .654 .739 240 25 38 Red
KDG-J2102 .740 .837 400 10 40 Brown
KDG-J2103 .838 .947 450 10 40 Green
KDG-J2104 .948 1.071 500 10 40 Black
KDG-J2105 1.072 1.212 700 10 40 Purple

Conductor may be right-hand lay or left-hand lay

 

Distribution Grip Dead-end for Jacketed Conductors (Coated)

Catalog Number Cable Range (inches) Wt. /Lbs. Per100 Units per carton Length (inches) Color Code
Min Max
KND-T500 .243 .253 13 100 16 Green
KND-T501 .254 .264 14 100 17 Red
KND-T502 .265 .272 14 100 17 Blue
KND-T503 .273 .284 14 100 18 Orange
KND-T100 .285 .297 15 100 19 Black
KND-T101 .298 .310 17 100 19 Yellow
KND-T102 .311 .323 18 100 20 Blue
KND-T103 .324 .338 18 100 20 Orange
KND-T104 .339 .354 20 100 21 Black
KND-T105 .355 .374 20 100 22 Yellow
KND-T106 .375 .397 25 100 23 Red
KND-T107 .398 .420 26 100 24 Green
KND-T108 .421 .445 40 50 27 Black
KND-T109 .446 .475 44 50 28 Orange
KND-T110 .476 .507 60 50 30 Blue
KND-T111 .508 .536 60 50 30 Red
KND-T112 .537 .572 68 50 31 Black
KND-T113 .572 .608 72 50 33 Yellow
KND-T114 .609 .648 96 25 33 Red
KND-T115 .649 .690 104 25 34 Green
KND-T116 .691 .735 120 25 35 Black
KND-T117 .736 .783 128 25 36 Orange
KND-T118 .784 .834 136 25 38 Blue
KND-T119 .835 .888 160 25 40 Black
KND-T120 .889 .945 176 25 42 Yellow
KND-T121 .946 1.005 204 25 44 Green
KND-T122 1.006 1.070 240 10 45 Red
KND-T123 1.071 1.138 240 10 47 Blue
KND-T124 1.139 1.212 300 10 48 Orange
KND-T125 1.213 1.288 300 10 49 Black
KND-T126 1.289 1.372 320 10 51 Yellow
KND-T127 1.373 1.458 380 10 53 Green
KND-T128 1.459 1.550 400 10 56 Red

Conductor may be right-hand lay or left-hand lay

 

Accessories

Thimble Clevis
Material: Ductile Iron Castings

Part Number RTS (KN) Weight (Kg) Dimension(mm)
A B C D E
TCB-11-B 50 0.5 60 45 20 40 M16
TCB-17-B 70 0.6 60 45 20 42 M16
TCB-27-B 120 0.9 107 48 24 57 M16
TCB-35-B 160 1.4 124 57 27 64 M16
TCB-42-B 190 1.4 124 57 27 64 M18